Three Phase Ups Uninterruptible Power Supply System 8-80KW With PDU Series Feeder

Ask Latest Price
Video Channel
Brand Name :CONSNANT
Model Number :CND310
Certification :CE, ISO9001, ISO14001
Place of Origin :Shenzhen, China
MOQ :1
Price :Negotianle
Payment Terms :T/T, L/C, Western Union
Supply Ability :100 sets per month
Packaging Details :Export Standard Package
Capacity :10-100KVA , 8-80KW
AC In. Frequency Range :50/60Hz±10%
AC In. PF. :0.95(with input filter)
Bypass In. Vol. Range :220V /380V±15%
Out. Volt. Range :220V±1%(steady load) 220V±3%( fluctuating load)
Output PF. :0.8
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Power System Telemechanics Electricity UPS System With PDU Series Feeder


Electricity UPS System consist of:

Electrical UPS, DBW bypass stablalized cabinet, and feeder cabinet of PDU series.

Product Introduction:

It possesses on-line double conversion and zero switch function. After being isolated and filtered by regulator, Single-phase 220V or three-phase 380V can provide stable power for load through inverter when the AC is normal. If the failure of AC power grid supply or a power cut occurs, direct current panel, the backup of power system, can invert to supply electricity through non-return diode. If the direct current panel is under voltage or cut off, static switch can shift to bypass stabilized cabinet to supply electricity. When the AC power becomes normal, the static switch automatically shift to AC power grid to supply electricity reversely. If the inverter is overloaded or the fault occurs to it, the static switch shift to bypass stabilized cabinet to supply electricity and indicates a warning signal at the same time.


Key Features:

  • Adopt full digital control technology
  • Intelligent detection and monitoring function
  • Digitally control the static switch with zero switch
  • Full isolation between input and output
  • Super low output zero earth voltage
  • DC UPS isolated with utility power completely
  • Cubical design with power standard (customization)
  • Multifunctional protection for overvoltage, under voltage, over current, short circuit and over temperature and so on.
  • Large-screen LCD monitor with Chinese and English operation interface
  • Ultralong 256 event record, user-friendly analysis and management to the situation of the power supply (touch screen optional)
  • Static bypass has a strong anti-overload capability


Mainly Application:

Power system telemechanics, PTU, power line communication, power system monitoring and etc


Specification:

CND310 10KVA-100KVA
Model (KVA) 10 15 20 30 40 50 60 80 100
Rating capacity(KW) 8 12 16 24 32 40 48 64 80
Rating voltage 220V(one-phase) /380V(three phase)
AC input
Voltage range ±25%
Frequency range 50,60Hz±10%
Soft start 0-100% in 5”
Power factor 0.95(with input filter)
Bypass input
Permitted voltage range ±15%
Frequency range 50/60Hz±5%
Output
Voltage accuracy 220V±1%(steady load) 220V±3%( fluctuating load)
Permitted Frequency range 50/60Hz±0.05Hz(powered by battery)
Power factor 0.8
THD Linearload<2%, non linear load<4%
Dynamic transients <5%
Current crest ratio 3:1
Overload capacity Normal in 110% load, 125% for 10min
Efficiency Double switch:94%, ECO:98%
DC
Battery voltage 220V
Cutoff voltage 185V
Maximum discharge current 36A 55A 73A 109A 145A 181A 218A 291A 364A
Penal display
LCD Chinese/English UPS status, operation instruction input voltage, output voltage, current, frequency, battery voltage, value of charge and discharge current, accident display, warning
Unique option

  1. SNMP card
  2. Dry contact card
  3. Signal transmitter
  4. Bypass isolation and voltage regulation
  5. Increase feeder circuit (standard for 8 loops)
  6. 12 pulse rectifier
  7. The appearance of special models(standard dimension:800×600×2260mm)
Environment
Temperature 0ºC-40 ºC
Humidity 0-95%(no condensing)
Storage temperature -25 ºC—55 ºC
Altitude <1500m