Function Key :
Function Key | Description |
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
Rack Mount Inverter Technical Parameter :
Model | 3.5KW | 5.5KW |
Input Voltage Waveform | Sinusoidal (utility or generator) | |
Nominal Input Voltage | 230Vac | |
Low Loss Voltage | 170Vac±7V(UPS);90Vac±7V(Appliances) | |
Low Loss Return Voltage | 180Vac±7V(UPS);100Vac±7V(Appliances) | |
High Loss Voltage | 280Vac±7V | |
High Loss Return Voltage | 270Vac±7V | |
Max AC Input Voltage | 300Vac | |
Nominal Input Frequency | 50Hz/60Hz(Auto detection) | |
Low Loss Frequency | 40±1Hz | |
Low Loss Return Frequency | 42±1Hz | |
High Loss Frequency | 65±1Hz | |
High Loss Return Frequency | 63±1Hz | |
Output Short CircuitProtection | Circuit Breaker | |
Efficiency (Mains Mode) | > 95%(Rated load, battery full charged) | |
Transfer Time | 10ms typical(UPS);20ms(Appliances) |
Model | 3.5KW | 5.5KW |
Rated Output Power | 3.5KW | 5.5KW |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac±5% | |
Output Frequency | 50Hz | |
Peak Efficiency | 93% | |
Overload Protection | 5s@±150%load;10s @110%~150%load | |
Surge Capacity | 2* rated power for 5 seconds | |
Nominal DC Input Voltage | 24.0Vdc | 48.0Vdc |
Cold Start Voltage | 23.0Vdc | 46.0Vdc |
Low DC Warning Voltageload<50%load≥50% | 23.0Vdc | 46.0Vdc |
22.0Vdc | 44.0Vdc | |
Low DC Warning ReturnVoltageload<50%load≥50% | 23.5Vdc | 47.0Vdc |
23.0Vdc | 46.0Vdc | |
Low DC Cut-off Voltageload<50%load≥50% | 21.5Vdc | 43.0Vdc |
21.0Vdc | 42.0Vdc | |
High DC Recovery Voltage | 32.0Vdc | 62.0Vdc |
High DC Cut-off Voltage | 33.0Vdc | 63.0Vdc |
No Load PowerConsumption | <35W |